RS2-FX/FX (NAVY) |
|
|
|
|
|
|
|
|
|
|
Product description |
|
|
|
|
|
|
|
|
|
|
|
Port type and quantity |
|
|
|
5 x 10/100Base-TX, TP cable, RJ45 sockets, auto-negotiation, auto-polarity 2 x 100Base-FX, MM cables, SC sockets |
|
|
|
|
|
|
|
Type |
|
|
|
RS2-FX/FX (NAVY) |
|
|
|
|
|
|
|
Order No. |
|
|
|
943 653-302 |
|
|
|
|
|
|
|
More Interfaces |
|
|
|
|
|
|
|
|
|
|
|
Power supply/signaling contact |
|
|
|
1 plug-in terminal block, 5-pin |
|
|
|
|
|
|
|
V.24 interface |
|
|
|
1 x RJ11 socket |
|
|
|
|
|
|
|
Standby port |
|
|
|
1 x RJ45 socket |
|
|
|
|
|
|
|
Network size - length of cable |
|
|
|
|
|
|
|
|
|
|
|
Twisted pair (TP) |
|
|
|
0 - 100 m |
|
|
|
|
|
|
|
Multimode fiber (MM) 50/125 µm |
|
|
|
0 - 5000 m 8 dB link budget at 1300 nm A = 1 dB/km, 3 dB reserve, B = 800 MHz*km |
|
|
|
|
|
|
|
Multimode fiber (MM) 62.5/125 µm |
|
|
|
0 - 4000 m 11 dB link budget at 1300 nm A = 1 dB/km, 3 dB reserve, B = 500 MHz*km |
|
|
|
|
|
|
|
Network size - cascadibility |
|
|
|
|
|
|
|
|
|
|
|
Line - / star topology |
|
|
|
Any |
|
|
|
|
|
|
|
Ring structure (HIPER-Ring) |
|
|
|
50 (reconfiguration time < 0.5 sec.) |
|
|
|
|
|
|
|
Power requirements |
|
|
|
|
|
|
|
|
|
|
|
Operating voltage |
|
|
|
24 V DC (-25% to +30%) |
|
|
|
|
|
|
|
Current consumption at 24 V DC |
|
|
|
Max. 800 mA |
|
|
|
|
|
|
|
Service |
|
|
|
|
|
|
|
|
|
|
|
Diagnostics |
|
|
|
LEDs (power, link status, data, error, standby, redundancy manager), Connection mirroring, Signal contact (24V DC / 1 A) |
|
|
|
|
|
|
|
Configuration |
|
|
|
Terminal SW, BootP, DHCP, auto-configuration adapter (ACA11) |
|
|
|
|
|
|
|
Security |
|
|
|
Port security |
|
|
|
|
|
|
|
Other services |
|
|
|
Prioritization of Unicast messages (2 queues), Multicast filtering (GMRP) |
|
|
|
|
|
|
|
Redundancy |
|
|
|
|
|
|
|
|
|
|
|
Redundancy functions |
|
|
|
Redundant 24 V power supply, HIPER-Ring (ring structure), redundant coupling |
|
|
|
|
|
|
|
Ambient conditions |
|
|
|
|
|
|
|
|
|
|
|
Operating temperature |
|
|
|
0 °C to +60 °C |
|
|
|
|
|
|
|
Storage/transport temperature |
|
|
|
-25 °C to +70 °C |
|
|
|
|
|
|
|
Relative humidity (non-condensing) |
|
|
|
10% to 95% |
|
|
|
|
|
|
|
Mechanical construction |
|
|
|
|
|
|
|
|
|
|
|
Dimensions (W x H x D) |
|
|
|
110 mm x 131 mm x 111 mm |
|
|
|
|
|
|
|
Mounting |
|
|
|
Top-hat rails |
|
|
|
|
|
|
|
Weight |
|
|
|
850 g |
|
|
|
|
|
|
|
Protection class |
|
|
|
IP20 |
|
|
|
|
|
|
|
Mechanical stability |
|
|
|
|
|
|
|
|
|
|
|
IEC 60068-2-27 shock |
|
|
|
15 g, 11 ms duration, 18 shocks |
|
|
|
|
|
|
|
IEC 60068-2-6 vibration |
|
|
|
1 mm (2 Hz - 13.2 Hz resonance frequencies), 90 min. 0.7g (13.2 Hz -100Hz resonance frequencies), 90 min. 3.5 mm (3 Hz - 9 Hz), 10 cycles, 1 octave/min. 1g (9 Hz - 150 Hz), 10 cycles, 1 octave/min. |
|
|
|
|
|
|
|
EMC interference immunity |
|
|
|
|
|
|
|
|
|
|
|
EN 61000-4-2 electrostatic discharge (ESD) |
|
|
|
6 kV contact discharge, 8 kV air discharge |
|
|
|
|
|
|
|
EN 61000-4-3 electromagnetic field |
|
|
|
10 V/m (80 - 1000 MHz) |
|
|
|
|
|
|
|
EN 61000-4-4 fast transients (burst) |
|
|
|
2 kV power line, 1 kV data line |
|
|
|
|
|
|
|
EN 61000-4-5 surge voltage |
|
|
|
Power line: 2 kV (line/earth), 1 kV (line/line), 1kV data line |
|
|
|
|
|
|
|
EN 61000-4-6 conducted immunity |
|
|
|
3 V (10 kHz - 150 kHz), 10 V (150 kHz - 80 MHz) |
|
|
|
|
|
|
|
EMC emitted immunity |
|
|
|
|
|
|
|
|
|
|
|
FCC CFR47 Part 15 |
|
|
|
FCC CFR47 Part 15 Class A |
|
|
|
|
|
|
|
EN 55022 |
|
|
|
EN 55022 Class A |
|
|
|
|
|
|
|
Approvals |
|
|
|
|
|
|
|
|
|
|
|
Safety of industrial control equipment |
|
|
|
cUL 508 (E175531) |
|
|
|
|
|
|
|
Hazardous locations |
|
|
|
cUL 1604 Class 1 Div 2 (E203960) |
|
|
|
|
|
|
|
Safety of information technology equipment |
|
|
|
cUL 60950 (E168643) |
|
|
|
|
|
|
|
Germanischer Lloyd |
|
|
|
Germanischer Lloyd (15662-00HH) |
|
|
|
|
|
|
|
Scope of delivery and accessories |
|
|
|
|
|
|
|
|
|
|
|
Scope of delivery |
|
|
|
Device, terminal block, operating manual |
|
|
|
|
|
|
|
Frontend Module |
|
|
|
|
|
|
|
|
|
|
|
Modulation |
|
|
|
Serial interface, web interface SNMPv1 |
|
|
|
|